Staging Inhibits
When the stage threshold is exceeded, a stage inhibit is applied. The stage inhibit calculates the rate of
recovery over a 10 minute period and determines if the next stage is required to meet the current
demand. If the rate of recovery is great enough, a new 10 minute inhibit is enabled. The unit will not go
to the next stage of operation until it determines that the current stage cannot satisfy the current
demand. Stage inhibits apply only between compressor stages and compressor heat to Aux indoor
heat. Stage inhibits do not apply to non-compressor heat stages. Stage inhibits are disabled by
navigating to Installer Setup > Comfort Settings > Aggressive Recovery. See examples of staging
inhibits below.