BAS-SVX078E-EN
Specifications
Specification Description Specification Description
Touch Screen Display
4.15 inches x 2.65 inches
(4.3 inches diagonal)
Auxiliary Heat Lockout
32°F to 70°F
Configurations
Heat/cool
Dual fuel
Heat only
Cooling only
Heat pump
Compressor Heat Lockout
5°F to 70°F
Maximum Number of Stages
Conventional: Three
heat/two cool
Heat pump: Two
compressors, three
auxiliary heat
Cooling Setpoint
Temperature Range
60°F to 99°F, 1°F resolution
Storage/Operating
Temperatures
-40°F to 175°F, 5% to 95%
RH non-condensing
Heating Setpoint
Temperature Range
55°F to 99°F, 1°F resolution
Input Power
24 Vac
Indoor Temperature Display
Range
-40°F to 122°F
Power Consumption 3 VA typical, 7 VA maximum
Outdoor Temperature
Display Range
-40°F to 147°F
Wire Usage
18 AWG (300 ft maximum for
remote sensors)
Indoor Humidity Display
Range
0% to 100%, 1% resolution
System Modes
Auto
Heating
Cooling
Off
Minimum Cycle Off Time
Compressor; 5 minutes
Indoor Heat; 1 minute
Fan Modes
Auto
On
Mobile App operating system
Android and iOS
Binary Input Open state
In order for the Binary Input
to recognize an open signal,
the external device, such as
mechanical relay contacts
(recommended gold-plated
contacts), switch, solid state
relay, or opto-isolator outputs
must provide an open signal
that measures greater than
330K ohms —preferably
near infinite ohms. Binary
Inputs are polarity sensitive,
which may affect solid state
relay and opto-isolator output
operation.
Binary Input Closed state
In order for the Binary Input
to recognize a closed signal,
the external device, such as
mechanical relay contacts
(recommended gold-plated
contacts), switch, solid state
relay, or opto-isolator outputs
must provide a closed signal
that measures less than 3.0K
ohms preferably near 0
ohms. Binary Inputs are
polarity sensitive, which may
affect solid state relay and
opto-isolator output
operation.
Wi-Fi
Pivot supports IEEE
802.11b/g/n, 2.4GHz only.
Ethernet
Pivot supports IEEE 802.3
Relay contact rating 2 Amps, 24 Vac