EasyManuals Logo
Home>Trane>Chiller>Sintesis RTAF HE series

Trane Sintesis RTAF HE series User Manual

Trane Sintesis RTAF HE series
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #147 background imageLoading...
Page #147 background image
RLC-SVX19G-GB
147
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
Evaporator Glycol Requirement
Table 25 – Leaving water temperature cutout & glycol mass percent recommended for RTAF chillers with
Standard tubes
Ethylene Glycol
Unit type
∆T evaporator
coolant (K)
2 3 4 5 6 7 8
LWT (°C) LWTC (°C) %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol
4 1.2 - 4 4 4 4 4 5
2 -0.8 - 8 8 9 10 12 -
0 -2.8 13 13 13 15 19 - -
-2 -4.8 18 18 19 - - - -
-4 -6.8 22 22 - - - - -
-5 -7.8 24 25 - - - - -
-6 -8.8 25 29 - - - - -
-7 -9.8 27 - - - - - -
-8 -10.8 29 - - - - - -
-9 -11.8 31 - - - - - -
-10 -12.8 - - - - - - -
-11 -13.8 - - - - - - -
-12 -14.8 - - - - - - -
Table 26 – Leaving water temperature cutout & glycol mass percent recommended for RTAF chillers with
Standard tubes
Monopropylene Glycol
Unit type
∆T evaporator
coolant (K)
2 3 4 5 6 7 8
LWT (°C) LWTC (°C) %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol %wt Glycol
4 1.2 - 4 4 4 4 5 -
2 -0.8 10 9 10 12 - - -
0 -2.8 15 16 21 - - - -
-2 -4.8 20 - - - - - -
-4 -6.8 27 - - - - - -
-5 -7.8 - - - - - - -
-6 -8.8 - - - - - - -
-7 -9.8 - - - - - - -
-8 -10.8 - - - - - - -
The table above is for RTAF sizes 090 to 245. For RTAF sizes 250 to 550, please consult your local Trane Sales Office.
Evaporator Waterside (not for free cooling version)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Sintesis RTAF HE series and is the answer not in the manual?

Trane Sintesis RTAF HE series Specifications

General IconGeneral
BrandTrane
ModelSintesis RTAF HE series
CategoryChiller
LanguageEnglish

Related product manuals