RLC-SVX19G-GB
4
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Introduction
Foreword
These instructions are given as a guide to good practice in
the installation, start-up, operation, and maintenance by
the user, of Trane RTAF chillers, manufactured in France. A
separate manual is available for the use and maintenance
of the unit’s control, Tracer™ UC800. They do not contain full
service procedures necessary for the continued successful
operation of this equipment. The services of a qualified
technician should be employed through the medium of a
maintenance contract with a reputable service company.
Read this manual thoroughly before unit start-up.
Units are assembled, pressure tested, dehydrated, charged
and tested in accordance with factory standard before
shipment.
Warnings and Cautions
Warnings and Cautions appear at appropriate sections
throughout this manual. Your personal safety and the
proper operation of this machine require that you follow
them carefully. The constructor assumes no liability
for installations or servicing performed by unqualified
personnel.
WARNING: Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe practices
or for equipment or property-damage-only accidents.
Safety Recommendations
To avoid death, injury, equipment or property damage, the
following recommendations should be observed during
maintenance and service visits:
1. The maximum allowable pressures for system leak testing
on low and high pressure side are given in the chapter
“Installation”. Insure to do not exceed test pressure by using
appropriate device.
2. Disconnect all power supplies before any servicing on
the unit.
3. Service work on the refrigeration system and the
electrical system should be carried out only by qualified and
experienced personnel.
4. To avoid any risk, it is recommended to place the unit on
an area with limited access.
Reception
On arrival, inspect the unit before signing the delivery note.
Specify any visible damage on the delivery note, and send
a registered letter of protest to the last carrier of the goods
within 7 days of delivery.
Notify the local TRANE sales office at the same time.
The delivery note must be clearly signed and countersigned
by the driver.
Any concealed damage shall be notified by a registered
letter of protest to the last carrier of the goods within
7 days of delivery. Notify the local TRANE sales office
at the same time.
Important notice: No shipping claims will be accepted by
TRANE if the above mentioned procedure is not respected.
For more information, refer to the general sales conditions
of your local TRANE sales office.
Note: Unit inspection in France. Delay to send registered
letter in case of visible and concealed damage is only
72 hours.
Loose Parts Inventory
Check all the accessories and loose parts that are shipped
with the unit against the shipping list. Included in these
items will be the water vessel drain plugs, rigging and
electrical diagrams, service literature, which are placed
inside the control panel and/or starter panel for shipment.
If optional elastomeric isolators are ordered with the unit
(model number digit 42 =1) they are shipped mounted on
the horizontal support frame of the chiller. The isolators’
location and distribution weight diagram is placed with
the service literature inside the starter/control panel.
Warranty
Warranty is based on the general terms and conditions of
the manufacturer. The warranty is void if the equipment is
repaired or modified without the written approval of the
manufacturer, if the operating limits are exceeded or if the
control system or the electrical wiring is modified. Damage
due to misuse, lack of maintenance or failure to comply
with the manufacturers instructions or recommendations
is not covered by the warranty obligation. If the user does
not conform to the rules of this manual, it may entail
cancellation of warranty and liabilities by the manufacturer.
Startup MUST be performed by Trane, or an authorized
agent of Trane, to VALIDATE this WARRANTY. Contractor
must provide a two-week startup notification to Trane (or an
agent of Trane specifically authorized to perform startup).
Unit Description
The Sintesis RTAF units are helical-rotary type, air-cooled
chillers designed for outdoor installation. The refrigerant
circuits are factory-piped, leak tested and dehydrated. Every
unit is electrically tested for proper control operation before
shipment.
Chilled water inlet and outlet openings are covered for
shipment. The Sintesis RTAF features Tranes exclusive
Adaptive Control™ logic, which monitors the control
variables that govern the operation of the chiller unit.
Adaptive control logic can adjust capacity variables to avoid
chiller shutdown when necessary, and keep producing
chilled water. The units feature two independent refrigerant
circuits. On the HSE HSS version, 1 compressor per circuit
is controlled by a dedicated variable speed Adaptive
Frequency Drive. Each refrigerant circuit is provided
with filter, sight glass, electronic expansion valve, and
charging valves. The shell-and-tube CHIL™ (Compact-High
performance-Integrated design-Low charge) evaporator is
manufactured in accordance with the Pressure Equipment
Directive (PED) code. Each evaporator is fully insulated and
equipped with water drain and vent connection.
Units are shipped with full oil charge and can be ordered
with either a factory refrigerant charge or optional
refrigerant pre-charge.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Sintesis RTAF HE series and is the answer not in the manual?

Trane Sintesis RTAF HE series Specifications

General IconGeneral
BrandTrane
ModelSintesis RTAF HE series
CategoryChiller
LanguageEnglish

Related product manuals