CHS-SVX02C-EN 13
RSAU0025F2 AHU
Model Number ..........................................................TCPA
Water Connection Size ............................. 2.5 in Victaulic
Ambient Operating Conditions
1
........................14–104°F
Supply Motor(s) ..................................................(2) 15 hp
OCP Device ................................................Circuit Breaker
Number of Electrical Circuits ..........................................1
Discharge Configuration.................................. Horizontal
Flex Duct Connection Size............................. 19 in round
Number of Discharge Air Connections ..........................2
Max Discharge Static Pressure ........................6.0 in ESP
Number of Return Air Connectors..................................3
Filter Rack (Qty. and size)
2
... (4) 24 in x 24 in, (2) 24 in x 12 in
Nominal Air Flow (cfm) .........................................10,000
Min/Max Air Flow (cfm)
3
..............................1,700/11,200
Selection is required for actual AHU performance.
1
For ambient conditions below 40°F, glycol is recommended.
2
Unit provided with standard 2 in filters. Filter rack will accept up to 95%
efficient MERV 14 filters.
3
Min/Max airflow is dependent upon external static pressure requirement.
Contact Rental Services for specific airflow and static pressure information.
Electrical Data
Voltage ........................................................ 460V 3-phase
Frequency ..................................................................60 Hz
Electrical Connection Type......................Cam Type Only
SCCR .............................................................................
65K
Minimum Circuit Ampacity (MCA) ....................54 amps
Maximu
m Overcurrent Protection (MOP)..........70 amps
For additional electrical information, contact Trane Rental Services.
Air Flow (CFM) 10,000
Air Pressure Drop through Unit (in H
2
0) 3.63
Cooling Coil
Entering Air DB/WB Temp (°F) 84/77
Leaving Air DB/WB Temp (°F) 50.4/50.4
Fluid Flow GPM 146.65
Entering Water Temp (°F) 44
Leaving Water Temp (°F) 56
Coil Water Pressure Drop (ft H
2
0) 11.54
Sensible Capacity (MBH) 363.8
Total Capacity (MBH) 883
Coil Face Area (sq ft) 20
Coil Rows 10
Water Flow Rates
Minimum Maximum
CW Coil Flow (GPM) 30 292
CW Coil Pressure Drop (ft H
2
0) 0.62 41.5
Lifting Device: Fork Lift or Crane
Performance Data