UT-101
UNIVERSAL PROCESS INDICATOR CONTROLLER&
4
Noise
Filter
POWER
N
L
N
L
NC
RELAY-2
NO
C
NC
NO
C
RELAY-1
1 2 3 4 5 6 7 8 9
10
11
121314
20 19 18 17 16 15
+
-
RTD
mA
A
B
B
4-20mA
0-20mA
-
VDC
+
-
VDC
+
T/C
OUTPUT
(Analog Out)
RS - 485
TPS
24VDC
+
-
TRANSMITTER
SHORT FOR TRANS.
v
T
D- D+
SUPPLY
EPN
UT-101
INPUT
CAUTION
WIRING CONSIDERATION
Shielded twisted pair wire is used for all analog I/P, Process sensors RTD,
Thermo-couple, mV-mA DC, Volt DC, Linear input and Communication.
AILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULTF
IN INSTRUMENT DAMAGE
AC 230V, 50Hz
CAUTION
LINE VOLTAGE
This product is suitable for connection 110/230VAC, 50Hz or 12/24 VDC main power
supply. It is user responsibility to provide proper protection for the products electrical
protection .
when applying power to various instruments, make sure sufficient current is supplied.
otherwise the instruments may not start up due to the Voltage drop.
NOTE : 12VDC OR 24VDC SUPPLY CONTROLLERS ARE ALSO AVAILABLE IF REQUIRED ON DEMAND.
2.4 Wiring Diagram
AILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULTF
IN INSTRUMENT DAMAGE
96X48 & 48X96
96X48 & 48X96
SUPPLY
230 15VAC+
14
13
AC SUPPLY
PN
12
E
24 / 12 VDC
DC SUPPLY
14
13
B
RTD
PT-100 / 1000
6
7
8
B
A
J/K/R/S/T/E
+
-
Shorng
6
7
8
-
3 WIRE
8
9
10
11
T
mA Input
TPS 24VDC
Transmi er
TRANSMITTER
2 WIRE
8
9
10
11
T
mA Input
TPS 24VDC
Transmi er
TRANSMITTER
4 20mA / 0 20mA
~~
CURRENT[mA]
9
8
THERMO-
COUPLE
INPUT
0 VDC5 /10
~
VOLTAGE
V
5
6
7
8
OUTPUT-RELAY
RELAY - 1
Relay Contact :
5A@240VAC
NC
CNO
17
16
15
RELAY - 2
Relay Contact :
5A@240VAC
NC
CNO
20
19
18
OUTPUT- SSR
SSR - 1
16
15
24VDC@20mA
12VDC@20mA
SSR - 2
19
18
24VDC@20mA
12VDC@20mA
4~20/0~20mA
0~10/0~5VDC
4
3
V
RETRANSMISSION
RE-TRANSMISSION
COMMUNICATION
RS-485
2
1
COMMNICATION
D+ D-