EasyManuals Logo
Home>Vector>Controller>TRA-F12 A Series

Vector TRA-F12 A Series User Manual

Vector TRA-F12 A Series
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
TRA-F12x-A
CONFIGURATION
Doc: 70-00-0792B V1.3, 20220830 © Vector Controls GmbH, Switzerland Page 24-34
Subject to change without notice www.vectorcontrols.com
VECTOR
5.8 Control settings
5.8.1 Parameter 4xx overview
Par/Addr
Description
Data type / value
Default
R/W
P400
Heating mode
on/off valve: Switching differential (X
H
)
3-position valve: Proportional band (X
pH
)
See P203 for valve type
Multiplier: 10
0.1…10.0 °C
2.0 °C
R/
W
P401
Cooling mode
on/off valve: Switching differential (X
C
)
3-position valve: Proportional band (X
pC
)
See P203 for valve type
Multiplier: 10
0.1…10.0 °C
1.0 °C
R/
W
P402
Integral time
Note: For floor heating and chilled ceiling the
integral action is 60 times slower
0 = Integral disabled
10 … 1200 sec
Floor heating: 10 … 1200 min
300 sec
Floor h.:
60 min
R/
W
P403
Dead zone half span (in Comfort mode for
cooling and heating application [P200 = 6])
Multiplier: 10
0.1…5.0 °C
1.0 °C
R/
W
5.8.2 Proportional control (proportional band or switching differential)
The proportional control function calculates the output based on the difference between temperature set point and measured
room temperature. The proportional band (P-band) defines the difference between temperature set point and input required
to produce a 100% output. For example: a heating control sequence and a 2.0 °C P-band value will produce a 100% output
when the input temperature is 2.0 °C below temperature set point.
Proportional band (P-band) is the inverted proportional gain. Small P-band values lead to a fast reacting controller
(susceptible for oscillation). Large P-band values lead to a slow reacting controller.
5.8.3 Integral control (integral time)
The integral time is the time required to obtain the same manipulated variable as for the proportional action when using
only an integral action. The shorter the integral time, the stronger the correction is of the integral action.
󰇛󰇜

󰇛󰇛󰇜
󰇛
󰇜

󰇜

󰇛
󰇜
󰇛󰇜
󰇛󰇜 󰇛󰇜 󰇛󰇜

󰇛󰇜

The integral time can be set between 10 and 1200 seconds (20 minutes). The default value is 300 seconds (5 minutes).
For room temperature control the integral time should be chosen above 120 seconds (2 minutes), since the temperature
change needs in minimum several minutes to take place after heating or cooling valve was changed.
5.8.4 on/off control
The diagrams show the on/off control sequence for all applications except 4-pipe heating and cooling (P200 = 4) which is
explained below.
Parameters
Parameter Description
Valid values for given chart
P200
Application mode
Not 6 (0 - 5, 7 - 8)
P201
Enable electric heater
0 or 1
P203
Valve Type
0 (= on/off valve)
ON
OFF
T [°C]
X
H
W
Legend
X
H
Switching span heating
X
C
Switching span cooling
W Set point
X
C
ON
OFF
T [°C]
Heating mode
Cooling mode
DO5 or DO4
DO4
W

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vector TRA-F12 A Series and is the answer not in the manual?

Vector TRA-F12 A Series Specifications

General IconGeneral
BrandVector
ModelTRA-F12 A Series
CategoryController
LanguageEnglish

Related product manuals