Doc: 70-00-0792B V1.3, 20220830 © Vector Controls GmbH, Switzerland Page 26-34
Subject to change without notice www.vectorcontrols.com
5.8.7 Fan control in automatic mode (on/off control)
Note:
• Fan is off only if the valve (or electric heater) is turned off.
• This chart shows the fan control for 2-pipe and 4-pipe heating or cooling applications (P200 = 0 to 5).
For 4-pipe heating and cooling application (P200 = 6), the dead zone between heating and cooling switch point is
not depicted.
• This chart assumes P213 (Minimum fan speed in auto mode) is set to 0 = Fan off (default).
Fan speed 1 is aligned with on/off valve (or electric heater). If the valve (or electric heater) switches ON for
heating/cooling then the fan speed 1 is switched ON. If the valve (or electric heater) switches OFF then the fan speed is
switched OFF (in case P213 minimum fan speed in auto mode is 0)