Page 18
Dual-Float Discriminating Sensor Alarms
MMM DD, YYYY HH:MM XM
L1: HIGH LIQUID ALARM
MMM DD, YYYY HH:MM XM
L1: FUEL ALARM
(Flashing Red light)
(Flashing Yellow light)
ALARM
TEST
ALARM
TEST
MMM DD, YYYY HH:MM XM
L1: SENSOR OUT ALARM
MMM DD, YYYY HH:MM XM
L1: LIQUID ALARM
(Flashing Yellow light)
(Flashing Yellow light)
MMM DD, YYYY HH:MM XM
L1: SHORT ALARM
ALARM
TEST
ALARM
TEST
CAUSE:
The sensor at the location shown has
detected fuel vapor or liquid.
ACTION:
Investigate the cause of the alarm and
take appropriate action.
CAUSE:
The sensor at the location shown has
detected at least 8 inches of non-
hydrocarbon liquid.
ACTION:
Contact your VR Service Contractor for
advice.
CAUSE:
The sensor at the location shown
has detected at least 1 inch of non-
hydrocarbon liquid.
ACTION:
Contact your VR Service Contractor
for advice.
CAUSE:
The sensor at the location shown
has been disconnected or is
inoperative.
ACTION:
Contact your VR Service Contractor
for advice.