Page 21
Vacuum Sensor Alarms
MMM DD, YYYY HH:MM XM
s1: VACUUM WARNING
(Flashing Yellow light)
ALARM
TEST
MMM DD, YYYY HH:MM XM
s1: NO VACUUM ALARM
(Flashing Red light)
ALARM
TEST
(Flashing Red light)
ALARM
TEST
MMM DD, YYYY HH:MM XM
s1: COMMUNICATION ALARM
CAUSE:
There may be a leak in the monitored
interstitial space. There is a possibility
that a No Vacuum alarm will be posted
in the future.
ACTION:
Find and repair vacuum leak then
perform a Vac Sensor Manual Test
(Diag Mode).
CAUSE:
There is no vacuum in the interstitial
space.
ACTION:
Find and repair vacuum leak then per-
form a Vac Sensor Manual Test (Diag
Mode).
CAUSE:
Hardware failure - sensor or
interconnecting wiring to console.
ACTION:
Contact your VR Service Contractor
for advice.