EasyManuals Logo
Home>Vertiv>Power Supply>NetSure 531 A91

Vertiv NetSure 531 A91 User Manual

Vertiv NetSure 531 A91
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
Chapter 2 Installation Instruction 3
NetSure 531 A41, NetSure 531 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction
2.1 Safety Regulations
Certain components in this power system have hazardous voltage and current. Always follow the instructions below:
1. Only the adequately trained personnel with satisfactory knowledge of the power system can carry out the
installation. The most recent revision of these safety rules and local safety rules in force shall be adhered to during
the installation.
2. All external circuits that are below 48V and connected to the power system must comply with the requirements of
SELV as defined in IEC 60950.
3. Make sure that the power (mains and battery) to the system is cut off before any operations can be carried out
within the system subrack.
4. The power subrack shall be kept locked and placed in a locked room. The key keeper should be the one
responsible for the power system.
5. The wiring of the power distribution cables should be arranged carefully so that the cables are kept away from the
maintenance personnel.
2.2 Preparation
Unpacking inspection
The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done
by representatives of both the user and Vertiv Tech Co., Ltd.To inspect the equipment, you should open the packing
case, take out the packing list and check against the packing list that the equipment is correct and complete. Make
sure that the equipment is delivered intact.
Cables
The cable design should meet relevant industry standards.
It is recommended to use the RVVZ cables as AC cables. The cable should reach at least +70°C temperature
durability. With cable length shorter than 30 meters, the Cross-Sectional Area (CSA) calculation should be based on
the current density of 3.5A/mm
2
. The suggested CSA value is no less than the Table 2-1.
Table 2-1 Load cable CSA selection
AC MCB rated current
Max. battery current
Min. cable CSA
Max. cable length
125A
105A
35mm
2
50mm
2
100A
80A
25mm
2
50mm
2
63A
58A
16mm
2
25mm
2
The CSA of DC cable depends on the current flowing through the cable and the allowable voltage drop. To select the
battery cable CSA, see Table 2-2. Select the DC load cable CSA according to the Table 2-3.
Table 2-2 Battery cable CSA selection
Battery MCB rated current
Max. battery current
Min. cable CSA
Max. cable length (volt drop: 0.5V, with max. CSA)
125A
105A
35mm
2
6 m
63A
50A
16 mm
2
5 m
Note:
1. The specs are applicable at ambient temperature of 25°C. If the temperature is higher than this, the CSA of the cable should
be increased.
2. The battery cable should reach at least +90°C heat durability. It is recommended to use double-insulated copper-core flame
retardant cable as battery cable

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 531 A91 and is the answer not in the manual?

Vertiv NetSure 531 A91 Specifications

General IconGeneral
BrandVertiv
ModelNetSure 531 A91
CategoryPower Supply
LanguageEnglish

Related product manuals