Reading Error Codes
48
Reading Error Codes
When the Link 1000 detects a problem, an error code appears
in the numeric display. The display alternates between
showing the monitoring function you have selected and the
error code. The error code flashes until the error is corrected.
The following table lists each Error Code, describes the cause
of the error, and indicates the action to take, if any.
Error
Code Meaning
E01 High battery voltage shutdown
(Inverter/charger error)
Battery voltage has risen above 15.5 V for 12 V
inverters or above 31 V for 24 V inverters.
Check all charging sources (that is, solar panels,
alternators, etc.
E02 Low battery voltage shutdown
(Inverter/charger error)
Battery voltage has dropped below 10.5 V for 12 V
inverters or below 21 V for 24 V inverters.
Check for a dead battery or poor battery connections.
E03 Over temperature shutdown
(Inverter/charger error)
The inverter has overheated and shut down. It will reset
automatically after it has cooled sufficiently.
Make sure there is adequate ventilation around the
inverter.
E04 Battery overload
(Inverter/charger error)
The battery is excessively discharged or there is a
shorted battery.
See your inverter/charger owners manual for
information about charging excessively discharged
batteries.