VESDA-EVEU-A00 Product Guide
90 www.xtralis.com
7.7 Replacing the Sampling Module
Caution: Electrostatic discharge (ESD) precautions need to be taken prior to removing the fascia from
the detector. A wrist strap must be connected to the case of the detector (Figure7-7).
Attention : Les precausions contre le decharge electrostatique dois etre respecter avant d’ouvrir le panneau
du detecteur. Un bracelet doit être raccor au panneau du détecteur (Figure7-7).
Ensure the area around the Sampling Module is clear of dirt and debris prior to replacement.
Care must be taken during Sampling Module replacement. The Sampling Module must be correctly seated in
order for a correct seal to be established between the Sampling Module and the rest of the detector. It is
essential to ensure that the rubber seal on the underside of the Sampling Module is correctly in place.
Removing the Sampling Module
1. Turn off the 24V DC power to the detector.
2. Open the front door and remove the front fascia. Refer to Sections 7.2 and 7.4 for further information.
3. Disconnect the Sampling Module cable (Figure7-19).
Figure7-19: Disconnect the Sampling Module cable