LaserFOCUS VLF-500 Product Guide VESDA
®
34
1.8 Factory Defaults
Table 9 - Factory defaults
*For code-specific information, see Codes and Standards Information for Air Sampling Smoke
Detection on page iv.
Note: If installing the detector as an NF-compliant system, when the "AutoLearn smoke"
function is started, it is recommended to set the Fire1 threshold at a maximum value
of 1.15 %obs/m and disable the delays (or set to "Instant Fire").
Note: **If installing the detector as an NF-compliant system, with a configuration of 20
holes of 3mm on the pipe network, the Minor flow fault should be set at a minimum
of 90%.
Note: If installing the detector as a UL compliant system the alarm signal connected to the
control panel for the fire evacuation shall not be less than 2.0 %obs/m (0.64 %obs/
ft.).
Parameter Allowed values Default values
Alert Smoke Threshold 1 & 2 0.025% - 2.0% obs/m*
(0.008% - 0.625% obs/ft.)
0.08% obs/m
(0.025% obs/ft.)
Action Smoke Threshold 1 & 2 0.025% - 2.0% obs/m*
(0.008% - 0.625% obs/ft.)
0.14% obs/m
(0.0448% obs/ft.)
Fire-1 Smoke Threshold 1 & 2 0.025% - 20% obs/m*
(0.008% - 6.25% obs/ft.)
0.2% obs/m
(0.0625% obs/ft.)
Fire-2 Smoke Threshold 1 & 2 0.025% - 20% obs/m*
(0.008% - 6.25% obs/ft.)
2.0% obs/m
(0.625% obs/ft.)
Alert Verification Delay 1 & 2 0 - 60 seconds 10 seconds
Action Verification Delay 1 & 2 0 - 60 seconds 10 seconds
Fire 1 Verification Delay 1 & 2 0 - 60 seconds 10 seconds
Fire 2 Verification Delay 1 & 2 0 - 60 seconds 10 seconds
Alarm Latching Enable Enabled or Disabled Enabled
Fault Latching Enable Enabled or Disabled Disabled
Airflow – Major High Flow Fault 100% - 150% 130%
Airflow – Major Low Flow Fault 50% - 100% 70%
Airflow – Minor High Flow Fault 100% - 150% 120%
Airflow – Minor Low Flow Fault 50% to 100% 80%**
AutoLearn Smoke 15 min. – 15 days 14 days
AutoLearn Flow 15 min. – 15 days 14 days
Smoke Test Button Enable/Disable Disabled
Threshold set 1 and 2 Day (1) & Night (2) /
Disabled
Disabled