14 www.xtralis.com
3.3 Default Settings
Parameter Default Values Range Access Level
Minimum Maximum
Air flow Delay:
l High Urgent
l High Minor
l Low Minor
l Low Urgent
0 seconds
l 130%
l 120%
l 80%
l 70%
0 seconds
l 105%
l 105%
l 25%
l 25%
60 seconds
l 200%
l 200%
l 95%
l 95%
Adm
Aspirator Speed 3,000 rpm 3,000 rpm 4,200 rpm Adm
AutoLearn 14 days
0 Hours
0 Minutes
0 days
0 Hours
15 Minutes
15 days
23 Hours
59 Minutes
Adm
Display Mode Smoke Level n/a n/a Usr
Display Button
Lockout…Buttons
Enabled n/a n/a Adm
Communications:
l Open-ended loop
l Preferred Port
l Network Delay
l Health Check
None
A
15 seconds
45 seconds
n/a
n/a
10 seconds
40 seconds
n/a
n/a
45 seconds
60 seconds
Dst
Day Start 07:00:00 n/a n/a Adm
Night Start 19:00:00 n/a n/a Adm
Device ID Name & Number n/a n/a Adm
Event Log to View l Smoke level
l Alarms
l Faults
l User Action
n/a n/a Adm
Faults Latched Latched n/a n/a Adm
Filter Service Interval 731 days (2 years) 1 day (Dependent
upon environment)
3655 days (10 years)
Clean Room
Adm
Alarms Latched Latched n/a n/a Adm
Alert Threshold 0.08% obs/m
(0.025% obs/ft)
0.005% obs/m
(0.0016% obs/ft)
1.990% obs/m
(0.6218% obs/ft)
Adm
Action Threshold 0.14% obs/m
(0.044% obs/ft)
0.010% obs/m
(0.0031 obs/ft)
1.995% obs/m
(0.6234% obs/ft)
Adm
Fire 1 Threshold 0.2% obs/m
(0.063% obs/ft)
0.015% obs/m
(0.0046% obs/ft)
2% obs/m
(0.625% obs/ft)
Adm
Fire 2 Threshold 2% obs/m
(0.625% obs/ft)
0.02% obs/m
(0.0063% obs/ft)
20% obs/m
(6.25% obs/ft)
Adm
Isolate Reminder Beep On n/a n/a Adm
Reference detector:
l Reference Zone No.
l Dilution
l Delay
l 255
l 100%
l 2 minutes
l Selectable
l 1%
l 0 minutes
l Selectable
l 100%
l 15 minutes
Adm
Hardware Relays 7 7 12 Adm
Scan Sector Delay 10 seconds 8 seconds 15 seconds Adm
Scan Threshold 0.02% obs/m
(0.0063% obs/ft.)
n/a n/a
Table 3-2: Default settings and permissible thresholds

Other manuals for Xtralis VESDA VLS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xtralis VESDA VLS and is the answer not in the manual?

Xtralis VESDA VLS Specifications

General IconGeneral
BrandXtralis
ModelVESDA VLS
CategorySmoke Alarm
LanguageEnglish

Related product manuals