505428-YTG-V-0417
14 Johnson Controls Unitary Products
Unit Limitations
1. Rated in accordance with AHRI Standard 110, Range “A” Utilization Voltage.
†. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.
Condenser Unit limitations
Size
(Tons)
Model
Unit Voltage
Applied Voltage
1
Outdoor DB Temp
Cooling (°F)
Indoor DB Temp
Cooling (°F)
Outdoor DB Temp
Heating (°F)
Indoor DB Temp
Heating (°F)
Min Max Max Min
Max Min Max Min Max Min
090
(7.5)
PC
208/230-3-60 187 252
125 40 86 68 70 0 80 50
460-3-60 432 504
090
(7.5)
YC
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630
120
(10)
PC
208/230-3-60 187 252
125 40 86 68 70 0 80 50
460-3-60 432 504
120
(10)
YC/YD
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630
150
(12.5)
YC/YD
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630
180
(15)
PC/PD
208/230-3-60 187 252
125 40 86 68 70 0 80 50
460-3-60 432 504
180
(15)
YC/YD
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630
240
(20)
PD
208/230-3-60 187 252
125 40 86 68 70 0 80 50
460-3-60 432 504
240
(20)
YC/YD
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630
300
(25)
YC
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630

Table of Contents

Other manuals for York R-410A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York R-410A and is the answer not in the manual?

York R-410A Specifications

General IconGeneral
BrandYork
ModelR-410A
CategoryAir Conditioner
LanguageEnglish

Related product manuals