The capacity of the condensing unit shall meet or
exceed _____ Btuh at a suction temperature of _____
F. The power consumption at full load shall not exceed
_____ kW.
The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cooling
capacity of _____ Btuh or greater at conditions of
_____ cfm entering-air temperature at the evaporator at
_____ F wet bulb and _____ F dry bulb, and air
entering the condensing unit at _____F.
The system shall have an EER of _____ Btuh/ Watt or
greater at standard AHRI conditions.
Installer Shall
Furnish York® air-cooled condensing units, heat pump
or equivalent in accordance with the performance
schedule shown on the plans, and
Unit shall be stored and handled in accordance with unit
manufacturer's instructions.
Install each unit as shown on the plans in accordance
with the manufacturer’s recommendations and all
applicable national and local codes
Unit Construction
Constructed of zinc-coated, galvanized steel.
Exterior surfaces bonded and coated with baked
enamel finish by a powder paint process capable of
withstanding a minimum of 1000 salt spray hours
according to ASTM B117.
Cabinet screws that comply with ASTM B117 salt spray
test for a minimum of 750 hours.
Permanently attached heavy-gage perimeter base rails
with forklift slots and lifting holes.
Removable access panels to all internal components.
Separate access panel to controls.
Access panels to allow outdoor coil cleaning.
Compressor(s)
Hermetic scroll type, internally protected with high-
pressure relief and over temperature protection.
Two stage units operate in 50% capacity increments.
Suction gas cooled
Voltage range of ±10% of unit nameplate voltage.
Neoprene isolators minimize sound transmission and
vibration.
Belly-band crankcase heaters keep refrigerant from
diluting sump oil.
Full charge of compressor oil
Outdoor Condenser Unit Coils
Draw thru configuration
Constructed with Micro-channel aluminum fins and
aluminum tubing.
Heat Pump Unit Outdoor Unit Coils
Draw thru configuration
Constructed with aluminum plate fins mechanically
bonded to seamless internally enhanced copper tubes
with all joints brazed.
Condenser Fans
Direct driven propeller-type fans
Aluminum blades riveted to corrosion resistant steel
spider brackets.
Arranged for vertical air discharge.
Equipped with PVC coated steel wire safety guards.
Condenser Motors
Totally enclosed, air over cooled.
Inherent overload protection.
Permanently lubricated bearings.
Must cycle to allow cooling operation down to 40°F.
Refrigerant Piping
Solid core filter-drier(s) ship loose for field installation.
Liquid and suction line service valves with gauge ports.
Suction and discharge line service ports accessible
from unit. Ports capped for leak prevention.
Liquid line magnetic check valves
Holding charge of R410A refrigerant.
Electrical Requirements
Single-point connection electrical power.
Nominal unit electrical characteristics shall be _____ v,
3-ph, 60 Hz. The unit shall be capable of satisfactory
operation within voltage limits of ____ v to _____ v.
Condenser fan motors and secondary of transformers
shall be grounded.
Unit Controls
All 24-volt control circuit, powered by a 24 volt
transformer(s) and protected by a resettable breaker.
Conventional thermostat must provide operation for
both condensing units and heat pumps without an “O”
output from the thermostat.
Low voltage terminal strip for simple hook-up.
Compressor motor protection shuts down unit for motor
over-current, over-temperature or low voltage
conditions.

Table of Contents

Other manuals for York R-410A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York R-410A and is the answer not in the manual?

York R-410A Specifications

General IconGeneral
BrandYork
ModelR-410A
CategoryAir Conditioner
LanguageEnglish

Related product manuals