SECTION 7 – UNIT CONTROLS
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
7
TABLE 22 - NATIVE BACNET, MODBUS AND N2 COMMUNICATIONS DATA MAP
10
Remote Setpoint [99=Auto]
Sys 1 Remote Setpoint (SP Unit)
Remote Cooling Range (DAT Unit)
Sys 2 Remote Setpoint (SP Unit)
Remote Heating Setpoint (HP or YCWL HP)
AV7 1032 03,06,16 Div 10 ADF 7 None None
Remote Heatpump Mode [0=Pnl, 1=Cool, 2=Heat] (HP
or YCWL HP)
OOO
Remote Start/Stop Command [0=Stop, 1=Run]
Sys 1 Remote Start/Stop (SP Unit)
10 SS_SYS2
BV3 1540 01,03,05,06,15 N/A
BD 3 0/1 0/1 Sys 2 Remote Start/Stop (SP Unit) NNN
Leaving Chilled Liquid Temp
Entering Chilled Liquid Temp
Discharge Air Temp (DAT Unit)
Sys 1 Suction Temp (EEV, Cond Units, R-410a/R-454B)
Sys 1 Suction Superheat (EEV)
Sys 1 Run Time in seconds
Sys 1 Cooler Inlet Refrigerant Temp (R-407c)
Sys 1 Defrost Temperature (HP)
Anti-Coincident Timer in seconds
Sys 2 Suction Temp (EEV, Cond Units, R-410a/R-454B)
Sys 2 Run Time in seconds
Sys 2 Cooler Inlet Refrigerant Temp (R-407c)
Sys 2 Defrost Temperature (HP)
Sys 2 Suction Superheat (EEV)
03,04 x1 ADF 31 None None Number of Compressors SSS
SCROLL CHILLER/HEATPUMP/CONDENSING UNIT
Board: 031-02550Modbus RTU, BACnet MS/TP, N2 Data Map
Comments
C.MMC.13.11, C.MMC.14.11, C.MMC.16.12
C.MMC.13.11, C.MMC.14.11, C.MMC.16.13
N2 Metasys
Engineering Units Point List Code: S = Standard O = Optional N = Not Available
Version York P/N
C.MMC.13.23, C.MMC.14.23, C.MMC.16.23
Item
Ref
Num
BACnet Name
BACnet
Object
Instance
Modbus
Address
Modbus Data Type
Supported
Modbus
Scaling
(See Note 5)
New
Update Unit Control Mode
V14 add op code 19, fault code 31; V18 add R-454B; V21 rem tray heater, mod BD13 and BI10; V23 fc 32 added
031-02755-001, -003, -004
031-02755-001, -003, -004
031-02755-001, -003, -004
ANALOG WRITE POINTS
BINARY WRITE POINTS
ANALOG READ ONLY POINTS
Property of Johnson Controls, Inc.
Subject to change without notice.
1 of 4
02/11/2020