EasyManuals Logo

York YMC2 User Manual

York YMC2
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #123 background imageLoading...
Page #123 background image
JOHNSON CONTROLS
123
FORM 160.84-OM1
ISSUE DATE: 9/21/2017
5
SECTION 5 - MAINTENANCE
PREVENTATIVE MAINTENANCE
It is the responsibility of the owner to provide the nec-
essary daily, monthly and yearly maintenance require-
ments of the system.
In any operating system it is most important to pro-
vide a planned maintenance and inspection of its func-
tioning parts to keep it operating at its peak efficiency.
Therefore, the following maintenance should be per-
formed when prescribed.
IMPORTANT – If a unit failure occurs
due to improper maintenance during the
warranty period; Johnson Controls will
not be liable for costs incurred to return
the system to satisfactory operation.
Electrical Isolation
1. Isolate electrical power supply to the chiller from
the facility
2. Isolate the Power Panel battery from the Uninter-
rupted Power Supply by opening the Power Panel
disconnect switch.
3. Isolateplantuidowtothechilleratappropriate
valves or have refrigerant isolated to prevent free-
wheeling the driveline and generating electrical
energy from the permanent magnet rotor.
TABLE 13 - MAINTENANCE REQUIREMENTS
Procedure Daily Weekly Monthly Yearly Other
Record operating conditions (on applicable Log Form) X
Check operating parameters for indication of tube fouling or
refrigerant loss
X
Check three-phase voltage and current balance X
Check programmable operating setpoints and safety cut-outs.
Make sure they are correct for the application
X
Verify condenser and evaporator water ows X
Leak check and repair leaks as needed
1
X
Check and tighten all electrical connections X
Clean or backush VSD heat exchanger X
Replace VSD starter coolant X
Measure motor winding and insulation resistance X
Perform refrigerant analysis
1
X
Review operating data for trends which indicate increasing
vibration or power consumption. The MBC data includes 1 x
rotational speed vibration in displacement.
X
Clean tubes X
2
Perform Eddy current testing and inspect tubes 2-5 Years
For operating and maintenance requirements listed above, refer to appropriate service literature, or contact your local Johnson Controls
Service Ofce.
1
This procedure must be performed at the specied time interval by an Industry Certied Technician who has been trained and qualied
to work on this type of YORK equipment. A record of this procedure being successfully carried out must be maintained on le by the
equipment owner should proof of adequate maintenance be required at a later date for warranty validation purposes.
2
More frequent service may be required depending on local operating conditions.
MAINTENANCE REQUIREMENTS FOR YMC
2
CHILLERS

Table of Contents

Other manuals for York YMC2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YMC2 and is the answer not in the manual?

York YMC2 Specifications

General IconGeneral
BrandYork
ModelYMC2
CategoryChiller
LanguageEnglish

Related product manuals