JOHNSON CONTROLS
50
FORM 160.84-OM1
ISSUE DATE: 9/21/2017
SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
OVERVIEW
This screen displays information pertaining to the
power panel, which includes the uninterruptable power
supply (UPS) and storage battery for essential loads
necessary for shutdown during a line power loss.
DISPLAY ONLY
Control Voltage (LED)
Indicates the OptiView control voltage digital input
voltage is present, indicating line power is available.
Power Loss Time
Indicates the time in seconds while the OptiView con-
trol voltage digital input is low, indicating time without
line power for the present outage.
Motor Speed
Indicates the motor speed as reported from the MBC.
UPS Line / Charging (LED)
Indicates the UPS is in charging mode, using line
power to supply loads and any necessary current to the
power storage battery.
UPS Inverter (LED)
Indicates the UPS is providing power from the storage
battery.
UPS Fault (LED)
Indicates the UPS has faulted.
UPS Battery V+ (LED)
Indicates the UPS senses battery present
UPS Battery Voltage
Indicates the UPS battery voltage from available to the
UPS input.
UPS Inverter Enable (LED)
Indicates the presence of the signal from OptiView to
the UPS permitting the UPS to supply power from the
battery as needed upon loss of line power.
Power Panel Temperature
Indicates the ambient temperature inside the power
panel.
POWER PANEL SCREEN
LD17930a
FIGURE 15 - POWER PANEL SCREEN