JOHNSON CONTROLS
57
SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
FORM 160.84-OM1
ISSUE DATE: 9/21/2017
3
VSD Output Frequency
Displays the present output frequency to the motor.
Phase Rotation
Displays the phase rotation sequencing
Output Current Rating
Indicates VSD size reported from VSD.
Motor Run (LED)
Indicates the digital output from the controls is com-
manding the motor to RUN.
DC Bus Regulating (LED)
Indicates the VSD is regulating the DC Bus.
Precharge Complete (LED)
Indicates the VSD DC Bus has been pre-charged.
Input Current Limit (LED)
Indicates the chiller input current is at the Job FLA
limit.
Cooling System (LED)
Indicates the relay controlling the VSD water pump
output is energized.
Precharge Active (LED)
Indicates the VSD is pre-charging the DC Bus.
DC Bus Voltage
Displays the DC Bus voltage.
Total Supply kVA
Displays the total kilovolt-Amps measured by the VSD.
Input Voltage Peak (L1, L2, L3)
Displays the three-phase input peak voltages measured
by the VSD (Neutral to Line).
Input Voltage RMS (L1, L2, L3)
Displays the three-phase input RMS voltages across
each line.
Input Current RMS (L1, L2, L3)
Displays the three-phase input current values measured
by the VSD.
Output Voltage RMS (Phase A, B, C)
Displays the three-phase output RMS voltages across
each line.
Output Current RMS (Phase A, B, C)
Displays the three-phase output current values mea-
sured by the VSD.
Rectifier Baseplate Temperature (L1, L2, L3)
Displays the VSD input rectifier baseplate tempera-
tures at each phase.
Inverter Baseplate Temperature (Phase A, B, C)
Displays the VSD output inverter baseplate tempera-
tures at each phase.
Internal Ambient Temperature
Displays the ambient temperature inside the VSD cabi-
net from two sensors as reported by the VSD.
NAVIGATION
Home
Causes an instant return to the Home screen.
VSD
Causes an instant return to the VSD screen.