8.3.9 Interlocking for 1 1/2 CB BH
IP14173-1 v3
8.3.9.1 Application
M13570-3 v6
The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A,
BH_LINE_B) functions are used for lines connected to a 1 1/2 breaker diameter
according to figure
85.
WA1 (A)
WA2 (B)
QB1
QC1
QA1
QC2
QC9
QB6
QB9
QB2
QC1
QA1
QC2
QC3
QB6
QC3
QB62
QB61
QA1
QC1
QC2
QC9
QB9
BH_LINE_A
BH_LINE_B
BH_CONN
en04000513.vsd
IEC04000513 V1 EN-US
Figure 85: Switchyard layout 1 1/2 breaker
M13570-7 v4
Three types of interlocking modules per diameter are defined. BH_LINE_A and
BH_LINE_B are the connections from a line to a busbar. BH_CONN is the
connection between the two lines of the diameter in the 1 1/2 breaker switchyard
layout.
M13569-4 v4
For a 1 1/2 breaker arrangement, the modules BH_LINE_A, BH_CONN and
BH_LINE_B must be used.
8.3.9.2 Configuration setting
M13569-6 v5
For application without QB9 and QC9, just set the appropriate inputs to open state
and disregard the outputs. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
Section 8 1MRK 511 423-UEN A
Control
160 Bay control REC650 2.2 IEC
Application manual

Table of Contents