10.3 Liquid medium supervision SSIML
GUID-37669E94-4830-4C96-8A67-09600F847F23 v3
10.3.1 Identification
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation liquid monitoring function SSIML - 71
10.3.2 Application
GUID-140AA10C-4E93-4C23-AD57-895FADB0DB29 v6
Liquid medium supervision (SSIML) is used for monitoring the transformers and
tap changers. When the level becomes too low compared to the required value, the
operation is blocked to minimize the risk of internal failures. Binary information
based on the oil level in the transformer and the tap changer is used as input signals
to the function. In addition to that, the function generates alarms based on received
information.
10.3.3 Setting guidelines
GUID-0C8E498B-2A65-44ED-91D6-53EC72F49222 v2
The parameters for Liquid medium supervision SSIML can be set via local HMI or
Protection and Control Manager PCM600.
Operation: This is used to disable/enable the operation of liquid medium
supervision i.e. Off/On.
LevelAlmLimit: This is used to set the limit for a level alarm condition in the
transformer.
LevelLOLimit: This is used to set the limit for a level lockout condition in the
transformer.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in
the transformer.
TempLOLimit: This is used to set the limit for a temperature lockout condition in
the transformer.
tLevelAlarm: This is used to set the time delay for a level alarm indication, given in
s.
tLevelLockOut: This is used to set the time delay for a level lockout indication,
given in s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication,
given in s.
1MRK 511 423-UEN A Section 10
Monitoring
Bay control REC650 2.2 IEC 205
Application manual

Table of Contents

Other manuals for ABB 650 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB 650 series and is the answer not in the manual?

ABB 650 series Specifications

General IconGeneral
BrandABB
Model650 series
CategoryController
LanguageEnglish

Related product manuals