EasyManuals Logo
Home>ABB>Controller>650 series

ABB 650 series User Manual

ABB 650 series
320 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #306 background imageLoading...
Page #306 background image
The protection IED has effective filters for these transients, which gives secure and
correct operation with CVTs.
16.3 SNTP server requirements
GUID-588FCD12-C494-445E-8488-8287B34EFD9A v4
The SNTP server to be used is connected to the local network, that is not more than
4-5 switches or routers away from the IED. The SNTP server is dedicated for its
task, or at least equipped with a real-time operating system, that is not a PC with
SNTP server software. The SNTP server should be stable, that is, either
synchronized from a stable source like GPS, or local without synchronization.
Using a local SNTP server without synchronization as primary or secondary server
in a redundant configuration is not recommended.
16.4 PTP requirements
GUID-741CC863-D760-49D6-85B2-AFECA222A8C3 v1
For PTP to perform properly, the Ethernet equipment that is used needs to be
compliant with IEEE1588. The clocks used must follow the IEEE1588 standard
BMC (Best Master Algorithm) and shall, for instance, not claim class 7 for a longer
time than it can guarantee 1us absolute accuracy.
16.5 IEC/UCA 61850-9-2LE Merging unit requirements
SEMOD166590-11 v5
The merging units that supply the IED with measured values via the process bus
must fulfill the IEC/UCA 61850-9-2LE standard.
This part of the IEC 61850 is specifying “Communication Service Mapping
(SCSM) – Sampled values over ISO/IEC 8802”, in other words – sampled data
over Ethernet. The 9-2 part of the IEC 61850 protocol uses also definitions from
7-2, “Basic communication structure for substation and feeder equipment –
Abstract communication service interface (ACSI)”. The set of functionality
implemented in the IED (IEC/UCA 61850-9-2LE) is a subset of the IEC
61850-9-2. For example the IED covers the client part of the standard, not the
server part.
The standard does not define the sample rate for data, but in the UCA users group
recommendations there are indicated sample rates that are adopted, by consensus,
in the industry.
There are two sample rates defined: 80 samples/cycle (4000 samples/sec. at 50Hz
or 4800 samples/sec. at 60 Hz) for a merging unit “type1” and 256 samples/cycle
for a merging unit “type2”. The IED can receive data rates of 80 samples/cycle.
Note that the IEC/UCA 61850-9-2LE standard does not specify the quality of the
sampled values, only the transportation. Thus, the accuracy of the current and
Section 16 1MRK 511 423-UEN A
Requirements
300 Bay control REC650 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB 650 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB 650 series and is the answer not in the manual?

ABB 650 series Specifications

General IconGeneral
BrandABB
Model650 series
CategoryController
LanguageEnglish

Related product manuals