t t
INPUTn
OUTPUTn
IEC09000732-1-en.vsd
IEC09000732 V1 EN-US
Figure 102: BINSTATREP logical diagram
10.7.3 Setting guidelines
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
The pulse time t is the only setting for the Logical signal status report
(BINSTATREP). Each output can be set or reset individually, but the pulse time
will be the same for all outputs in the entire BINSTATREP function.
10.8 Fault locator LMBRFLO
IP14592-1 v2
10.8.1 Identification
M14892-1 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fault locator LMBRFLO - -
10.8.2 Application
M13752-3 v6
The main objective of line protection and monitoring IEDs is fast, selective and
reliable operation for faults on a protected line section. Besides this, information on
distance to fault is very important for those involved in operation and maintenance.
Reliable information on the fault location greatly decreases the downtime of the
protected lines and increases the total availability of a power system.
The fault locator is started with the input CALCDIST to which trip signals
indicating in-line faults are connected, typically distance protection zone 1 and
accelerating zone or the line differential protection. The disturbance report must
also be started for the same faults since the function uses pre- and post-fault
information from the trip value recorder function (TVR).
Beside this information the function must be informed about faulted phases for
correct loop selection (phase selective outputs from differential protection, distance
protection, directional OC protection, and so on). The following loops are used for
different types of faults:
1MRK 511 423-UEN A Section 10
Monitoring
Bay control REC650 2.2 IEC 219
Application manual

Table of Contents

Other manuals for ABB 650 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB 650 series and is the answer not in the manual?

ABB 650 series Specifications

General IconGeneral
BrandABB
Model650 series
CategoryController
LanguageEnglish

Related product manuals