13.6.2.1 Settings for RS485 and optical serial communication
M17109-118 v12
General settings
SPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM optical
serial port while DNP and IEC 60870-5-103 additionally can utilize the RS485
port. A single protocol can be active on a given physical port at any time.
Two different areas in the HMI are used to configure the IEC 60870-5-103
protocol.
1. The port specific IEC 60870-5-103 protocol parameters are configured under:
Main menu/Configuration/Communication/Station Communication/
IEC60870-5-103/
<config-selector>
SlaveAddress
BaudRate
RevPolarity (optical channel only)
CycMeasRepTime
MasterTimeDomain
TimeSyncMode
EvalTimeAccuracy
EventRepMode
CmdMode
RepIntermediatePos
<config-selector> is:
“OPTICAL103:1” for the optical serial channel on the SLM
“RS485103:1” for the RS485 port
2. The protocol to activate on a physical port is selected under:
Main menu/Configuration/Communication/Station Communication/Port
configuration/
RS485 port
RS485PROT:1 (off, DNP, IEC103)
SLM optical serial port
PROTOCOL:1 (off, DNP, IEC103, SPA)
Section 13 1MRK 511 423-UEN A
Station communication
262 Bay control REC650 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB 650 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB 650 series and is the answer not in the manual?

ABB 650 series Specifications

General IconGeneral
BrandABB
Model650 series
CategoryController
LanguageEnglish

Related product manuals