Section 9 Technical Data CP-C MM
M&I – AC 900F Controller 147
CP-C MM
Application
Input - supply circuits
Input - control circuit
Output
Monitoring function
CP-C MM Messaging module for CP-C
Rated voltage 110 - 240 V AC / 100 - 350 V DC
Voltage range 70 - 264 V AC / 80 - 350 V DC
Power consumption typ. 2.5 VA / 1.5 W
Type of triggering Volt-free triggering
Control input, REMOTE OFF control
function
Remote OFF
Switching-off threshold R ≤ 1 kΩ
Switching-on threshold R ≥ 10 kΩ
Input current Typ. 1 mA (200 mA for 200 µs)
Relay with change-over contacts 11-12/14, 21-22/24
Functional principle Closed-circuit principle
Max. switching voltage / current 250 V / 1 A
Min. switching voltage / current 24 V / 10 mA
Rated current at 24 V / 230 V 1 A, ohmic and inductive load
Switching cycle 0.1 x 10
6
Monitoring Low voltage detection
Input threshold value(s) 85 V AC / 90 V DC
Output threshold value(s) 20 V DC