Section 5 Mounting TU terminal blocks
M&I – AC 900F Controller 77
TU terminal blocks
When using a direct I/O, the corresponding number of I/O terminal blocks must be
connected on the right side of the CPU module using the previously attached
accessory part. The TA526 accessory part for wall mounting prevents any
deformation of the terminal block during fixing to the wall. It is recommended to
mount the terminal blocks in small groups of up to three units. After having marked
the correct position and drilled the bores, the terminal blocks can be fixed by means
of screws. Use two M4 screws per terminal block for this purpose. The screws must
be inserted at the terminal block front.
TA526 wall mounting.png