Section 5 Mounting Dimensional drawings of the CP-C 24/5.0 and CP-C 24/10.0
M&I – AC 900F Controller 81
Dimensional drawings of the CP-C 24/5.0 and CP-C 24/10.0
CP_C24_dimensional_drawing.png
Install the devices in upright position with the input terminals being arranged at the
bottom. In order to ensure sufficient convection cooling, the minimum distance to
other modules must not be less than 80 mm in vertical and 10 mm in horizontal
direction.