Chapter 3 – Electrical Installation
ACS/ACC/ACP 601 Frequency Converters 3-5
Cable Routing
The motor cable should be installed away from other cable routes.
Motor cables of several frequency converters can be run in parallel
installed next to each other. It is recommended that the motor cable,
mains cable and control cables be installed on separate trays
(minimum distance 500 mm). Long parallel runs of motor cable with
other cables should be avoided in order to decrease electromagnetic
interference caused by the rapid changes in the frequency converter
output voltage.
Where control cables must cross power cables make sure they are
arranged at an angle as near to 90 degrees as possible. Extra cables
should not be run through the ACx 600.
The cable trays shall have good electrical bonding to each other and to
the earthing eletrodes. Aluminium tray systems can be used to improve
local equalizing of potential.
Below is a diagram of cable routing
ACT PAR FUNC DRIVE
ENTER
LOC
REM
RESET REF
ACS 600
90 °
min 500 mm
Motor cable
Mains cable
Control cables
min 300 mm

Table of Contents

Other manuals for ABB ACS 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS 600 and is the answer not in the manual?

ABB ACS 600 Specifications

General IconGeneral
BrandABB
ModelACS 600
CategoryControl Unit
LanguageEnglish

Related product manuals