Appendix A – ACS/ACC/ACP 601 Technical Data
A-6 ACS/ACC/ACP 601 Frequency Converters
Input Power
Connection
Voltage (
U
1
):
380/400/415 VAC 3-phase
± 10 % for 400 VAC units
380/400/415/440/460/480/500 VAC 3-phase
± 10 % for 500 VAC units
525/550/575/600/660/690 VAC 3-phase
± 10 % for 690 VAC units
(690 VAC 3-phase
-10
...
+ 5 % for ACx 607 units)
Short Circuit Capability: The rated short time withstand current of
ACx 600 is 50 kA 1 s.
Measured according to US standards up to 400 kVA: Suitable for use in a
circuit capable of delivering not more than 65 kA rms symmetrical amperes at
480 V maximum (500 V units), and at 600 V maximum (690 V units).
Frequency: 48 to 63 Hz, maximum rate of change 17 %/s
Imbalance: Max.
± 3 % of nominal phase to phase input voltage
Fundamental Power Factor (cos
ϕ
1
): 0.97 (at nominal load)
Motor Connection
Voltage (
U
2
): 0 to
U
1
,
3-phase symmetrical
Frequency: DTC mode: 0 to 3.2 ·
f
FWP
. Maximum frequency 300 Hz.
f
FWP
=
f
FWP
: Frequency at field weakening point;
U
Nmains
: Mains (input power) voltage;
U
Nmotor
: Rated motor voltage;
f
Nmotor
: Rated motor frequency
Scalar Control mode (not for ACP 600): 0 to 300 Hz
With du/dt Filter (DTC and Scalar Control modes): 0 to 120 Hz
Frequency Resolution: 0.01 Hz
Current: see rating tables
Power Limit: 1.5 ·
P
hd
Overcurrent Trip: 3.5 ·
I
2hd
Field Weakening Point: 8 to 300 Hz
Switching Frequency: 3 kHz (average). In 690 V units 2 kHz
(average).
Maximum Recommended Motor Cable Length: 300 m (980 ft). This
is the cumulative length in case of parallel connected motors. For ACx
601-0005-3 to ACx 601-0016-3, ACx 601-0006-5 to ACx 601-0020-5
and ACx 601-0009-6 to ACx 601-0020-6, if the motor cable length
exceeds 70 metres (230 ft), an ABB representative should be
consulted.
Bearings of over 90 kW (125 HP) Motors: Insulated bearing at non-
driven end is recommended.
U
Nmains
U
Nmotor
·
f
Nmotor