Appendix A – ACS/ACC/ACP 601 Technical Data
ACS/ACC/ACP 601 Frequency Converters A-3
NEMA Ratings
The NEMA ratings for ACS 601 with 60 Hz supply are below. Symbols
are described on previous page.
Normal Use Heavy-duty Use
ACS 601
Type
Duty Cycle
1/5 min
Duty Cycle
1/5 min
Duty Cycle
1)
2/15 s
Frame
Type
I
2N
4/5min
[A]
I
2Nmax
1/5min
[A]
P
N
[HP]
I
2hd
4/5min
[A]
I
2hdmax
1/5min
[A]
I
2hd
13/15s
[A]
I
2hdmax
2/15s
[A]
P
hd
[HP]
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACS 601-0006-4 7.6 8.4 5 6.2 9.3 6.2 12.4 3 R2
ACS 601-0009-4 11 12 7.5 7.6 11 7.6 15.2 5
ACS 601-0011-4 15 17 10 11 17 11 22 7.5
ACS 601-0016-4 21 23 15 15 23 15 30 10 R3
ACS 601-0020-4 27 30 20 19 27 19 36 10
ACS 601-0025-4 34 37 25 24 36 24 48 15 R4
ACS 601-0030-4 41 45 30 31 47 31 62 20
ACS 601-0040-4 52 57 40 41 62 41 82 30 R5
ACS 601-0050-4 65 72 50 47 71 47 94 30
ACS 601-0060-4 77 85 60 58 87 58 116 40
ACS 601-0070-4 96 106 75 68 98 68 130 50 R6
ACS 601-0100-4 124 136 100 86 126 86 168 60
ACS 601-0120-4 156 172 125 113 168 113 224 75 R7
ACS 601-0140-4 180 198 150 141 203 141 270 100
Note: The US manufactured units are labelled to -4 types. The information in this
manual concerning the corresponding -5 type applies to them.

Table of Contents

Other manuals for ABB ACS 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS 600 and is the answer not in the manual?

ABB ACS 600 Specifications

General IconGeneral
BrandABB
ModelACS 600
CategoryControl Unit
LanguageEnglish

Related product manuals