Mechanical installation
33
Before installation
The drive must be installed in an upright position with the cooling section facing a
wall. Check the installation site according to the requirements below. Refer to
chapter Dimensional drawings for frame details.
Requirements for the installation site
See chapter Technical data for the allowed operation conditions of the drive.
Wall
The wall should be as close to vertical as possible, of non-flammable material and
strong enough to carry the weight of the unit. Check that there is nothing on the wall
to inhibit the installation.
Floor
The floor/material below the installation should be non-flammable.
Free space around the unit
Required free space around the drive to enable cooling air flow, service and
maintenance is shown below in millimetres and [inches].
IP 21 (UL 1)
50 [2.0]
50 [2.0]
200 [7.9]
Cooling air flow
200 [7.9]