EasyManuals Logo
Home>ABB>Adapter>FENA-01

ABB FENA-01 User Manual

ABB FENA-01
388 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
Modbus/TCPStart-up 61
FENA-01/-11/-21 configuration parameters – group C (group 3)
Note: The actual parameter group number depends on the drive
type. Group C (group 3) corresponds to:
parameter group 54 in ACS355
parameter group 52 in ACSM1, ACS850 and ACQ810
parameter group 52 in ACS880 and ACS580 if the adapter is
installed as fieldbus adapter A or group 55 if the adapter is
installed as fieldbus adapter B.
No.
1)
Name/Value Description Default
01 DATA IN 1
(drive to client)
Selects the drive parameter address from
which the data is read to the DATA IN 1
register (from the server to the client). The
Modbus register address maps are explained
in chapter Modbus/TCP – Communication
protocol.
The content is defined by a decimal number in
the range of 0 to 9999 as follows:
0 = None
ACS355:
FBA DATA IN 1
ACSM1:
FBA DATA IN1
ACS850/ACQ810:
FBA data in1
ACS880/ACS580:
FBA A/B data in1
0 = None Not used
101…9999 Parameter index with format xxyy, where
xx is the parameter group number (199)
yy is the parameter number index within
that group (0199).
Note: In ACS880 and ACS580, choose Other
to display a list of mappable drive parameters.
02
12
DATA IN 2
DATA IN 12
See parameter 01 DATA IN 1. 0 = None
1)
The number of parameters in this group may vary by drive type and drive firmware.
0 Not used
1…99 Virtual address area of drive
control. Not used when the
Modbus/TCP protocol is used.
101…
9999
Parameter area of the drive

Table of Contents

Other manuals for ABB FENA-01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB FENA-01 and is the answer not in the manual?

ABB FENA-01 Specifications

General IconGeneral
BrandABB
ModelFENA-01
CategoryAdapter
LanguageEnglish

Related product manuals