PROFINET IO – Start-up 249
FENA-01/-11/-21 configuration parameters – group A (group 1)
Note: The actual parameter group number depends on the drive
type. Group A (group 1) corresponds to:
• parameter group 51 in ACS355, ACSM1, ACS850 and
ACQ810
• parameter group 51 in ACS880 and ACS580 if the adapter is
installed as fieldbus adapter A or group 54 if the adapter is
installed as fieldbus adapter B.
No. Name/Value Description Default
01 FBA TYPE Read-only. Shows the fieldbus adapter type
as detected by the drive. The value cannot be
adjusted by the user.
If the value is 0 = None, the communication
between the drive and the module has not
been established.
128 =
ETHER-
NET
02 PROTOCOL/
PROFILE
Selects the application protocol and
communication profile for the network
connection.
The selections available for PROFINET IO
communication are listed below.
1)
0 = Modbus/TCP: ABB Drives profile -
Classic
0
1)
ACS355:
FB PAR 2
ACSM1:
FBA PAR2
ACS850/ACQ810:
FBA par2
ACS880/ACS580:
Protocol/Profile
10 = PNIO Pdrive PROFINET IO protocol: PROFIdrive profile
11 = PNIO ABB Pro PROFINET IO protocol: ABB Drives profile
12 = PNIO T16 PROFINET IO protocol: Transparent 16-bit
profile
13 = PNIO T32 PROFINET IO protocol: Transparent 32-bit
profile
14 = PNIO PdriveM PROFINET IO protocol: PROFIdrive
positioning mode