260 PROFINET IO – Start-up
FENA-01/-11/-21 configuration parameters – group C (group 3)
Note: The actual parameter group number depends on the drive
type. Group C (group 3) corresponds to:
• parameter group 54 in ACS355
• parameter group 52 in ACSM1, ACS850 and ACQ810
• parameter group 52 in ACS880 and ACS580 if the adapter is
installed as fieldbus adapter A or group 55 if the adapter is
installed as fieldbus adapter B.
No.
1)
Name/Value Description Default
01 DATA IN 1
(drive to master)
Selects data word 1 sent by the drive over the
PROFINET network. The content is defined by
a decimal number in the range of 0 to 9999 as
follows:
See also Virtual address area allocation with
ACSM1 on page 261.
4 or 14
2)
ACS355:
FBA DATA IN 1
ACSM1:
FBA DATA IN1
ACS850/ACQ810:
FBA data in1
ACS880/ACS580:
FBA A/B data in1
0 = None Not used
4 = SW 16bit Status word (16 bits)
5 = Act1 16bit Actual value ACT1 (16 bits)
6 = Act2 16bit Actual value ACT2 (16 bits)
14 = SW 32bit Status word (32 bits)
15 = Act1 32bit Actual value ACT1 (32 bits)
16 = Act2 32bit Actual value ACT2 (32 bits)
24 = SW2 16bit Status word 2 (16 bits)
101…9999 Parameter index with format xxyy, where
• xx is the parameter group number (1…99)
• yy is the parameter number index within
that group (01…99).
Note: In ACS880 and ACS580, choose Other
to display a list of mappable drive parameters.
0 Not used
1…99 Virtual address area of drive control
101…
9999
Parameter area of the drive