50 Modbus/TCP – Start-up
Drive configuration
The information in this section applies to all drive types compatible
with the adapter module, unless otherwise stated.
Modbus/TCP connection configuration
After the adapter module has been mechanically and electrically
installed according to the instructions in chapters Mechanical
installation and Electrical installation, you must prepare the drive
for communication with the module.
The detailed procedure of activating the module for Modbus/TCP
communication with the drive depends on the drive type. Normally,
you must adjust a parameter to activate the communication. See
the drive-specific start-up sections starting on page 63.
Once communication between the drive and the adapter module
has been established, several configuration parameters are copied
to the drive. These parameters are shown in the tables below and
must be checked first and adjusted where necessary. You can
adjust the parameters via a drive control panel, a PC tool or a web
user interface. For more information on the web user interface, see
Appendix C – FENA configuration web pages.
Note:
• Not all drives display descriptive names for the configuration
parameters. To help you identify the parameters in different
drives, the names displayed by each drive are given in gray
boxes in the tables.
• The new parameter settings take effect only when you power
up the module the next time or when you activate the fieldbus
adapter refresh parameter.