PROFINET IO – Start-up 263
Starting up fieldbus communication for ACS355
drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive with parameter 9802 COMM PROT SEL.
3. Set the module configuration parameters in group 51.
At the minimum, select the communication protocol and profile
with parameter 5102 and configure the network settings with
parameters 5103…5113.
4. With parameter 3018 COMM FAULT FUNC, select how the
drive reacts to a fieldbus communication break.
5. With parameter 3019 COMM FAULT TIME, define the time
between communication break detection and the selected
action.
6. Define the process data transferred to and from the drive in
parameter groups 54 and 55.
Note: The adapter module sets the Status word and actual
value automatically in parameters 5401 and 5402, and Control
word and reference in parameters 5501 and 5502.
7. Validate the settings made in parameter groups 51, 54 and 55
with parameter 5127 FBA PAR REFRESH.
8. Set the relevant drive control parameters to control the drive
according to the application.
Examples of appropriate values are shown in the tables below.

Table of Contents

Other manuals for ABB FENA-11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB FENA-11 and is the answer not in the manual?

ABB FENA-11 Specifications

General IconGeneral
BrandABB
ModelFENA-11
CategoryAdapter
LanguageEnglish

Related product manuals