ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 151
Function Time on OFF
This defines the Time function on Fan OFF.
None: No Time function is executed.
Switching delay: The fan is switched off after this delay.
Minimum time: The fan remains OFF for at least this time.
Selection of option Switching delay:
Dependent parameter:
Time in s [1…65,535 x 0.1]
The fan is switched off after this delay.
Selection of option Minimum time:
Dependent parameter:
Time in s [1…65,535]
The fan remains OFF for at least this time.
Enable communication object
"Forced operation" 1-bit
Yes: A 1 bit Forced operation communication object is enabled.
Dependent parameters:
Forced operation on object value
0: Forced operation is activated by a telegram with value 0.
1: Forced operation is activated by a telegram with value 1.
Reaction on forced operation
This parameter defines how the fan should respond to a forced operation.