ABB i-bus
®
KNX
Commissioning
152 2CDC508134D0202 | FCA/S 1.x.x.1
3.2.3.16 Parameter window Status messages (single speed)
This is the parameter window where status messages are defined.
This parameter window is visible if the option Enabled as fan has been selected under the parameter
Outputs E, F, G in Parameter window Enable output E...H, p. 123.
Enable communication object
"Status byte fan" 1-byte
Options:
No
Yes
From this status byte the states control values A or C, automatic, forced operation and the four limitations
are indicated directly via a 1-bit coding.
For further information see: Status byte fan, p. 258
Yes: The communication object Status byte fan is enabled.
Dependent parameter:
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only: The status is updated but not sent.
On change: The status is sent when a change occurs.
After request: The status is sent when a request occurs.
After a change or request: The status is sent on a change or a request.