ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 165
Enable communication object
"Status Switch" 1-bit
Selection of option Yes.
Dependent parameters:
Send object value
After a change or request
No, update only: The status is updated but not sent.
On change: The status is sent when a change occurs.
After request: The status is sent when a request occurs.
After a change or request: The status is sent on a change or a request.
Object value of contact position
This parameter defines the communication object value of the switch status (Status switch).
1 = Closed, 0 = Open: A closed contact is represented by communication object value 1 and
an open contact is represented by the value 0.
0 = Closed, 1 = Open: A closed contact is represented by communication object value 0 and
an open contact is represented by the value 1.
The contact position and thus the switch status can be the result of a series of priorities and
links.