ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 73
Enabled: The operating states Manual operation and KNX operation can be toggled via button .
Enable/disable via communication object: The communication object Block manual operation -
General appears.
Telegram value:
0 = Enable button
1 = Block button
Blocked: Manual operation is generally disabled
Reset from manual operation to
KNX operation
Options:
No
Yes
This parameter determines whether, after pressing the button , the device will remain in Manual
operation or will be reset back to KNX operation.
Yes: The device is reset to KNX operation.
Dependent parameter:
Time for automatic reset
to KNX operation in s [1...65,535]
Options:
1…30…65,535
This parameter determines how long, after pressing button , the device will remain in Manual
operation.
The device remains in Manual operation after the last button push until either button is pushed
again or the programmed time has timed out.