Distributed busbar protection REB500
Configuring output relay events
An event is generated when an output relay picks up or resets, i.e. this type of event
takes any reset delay that has been set or blocking by another signal into account.
Select an output relay in the overview dialog first by clicking on its label above the
signal list (its column is then highlighted). Now open the event configuration
dialog by clicking on the “CR event config.” button.
As in the case of the binary input signals in Section 3.6.3.2., the binary output
signals are configured at the works.
3.6.4 GOOSE input support
GOOSE indications from protection IED’s (e.g. Line protection trip) can be used as
input signals for REB500 functions (e.g. Start breaker failure protection).
Figure 33 illustrates a line fault combined with a breaker failure condition, and the
resulting information (trip signal) flow assumed that the REB500 starting input is
based on a GOOSE indication.