1MDU07212-YN Rev. C Section 2
REF601/REJ601 overview
REF601 / REJ601 9
Application Manual
Table 1: Relay functions, continue
Related products
REJ601 /
REF601
REJ601 /
REF601
REF601
Functionality ANSI IEC B C D
Protection
Phase discontinuity protection 46PD I2/I1> -
Negative
-
sequence overcurrent
protection
46 I2> - -
Circuit breaker failure protection
51BF/51
NBF
3I>/Io>B
F
-
Master trip 86
Master
Trip
Two setting group
Three phase transformer inrush
detector
68 3I2f>
Three
-
phase thermal protection for
feeders, cables and distribution
transformers
49 3Ith> -
Control (Function available in REF601 )
Breaker control functionality
I <
-
> O
CB
I <
-
> O
CB
Auto-reclosing 79 O -> I - -
Condition monitoring
Trip circuit supervision TCM TCS
Measurement
Three-phase current measurement 3I 3I
Residual current measurement In Io
Negative phase sequence current I2 I2 - -
Thermal level ϑ ϑ -
Operation counter - - -
= Included
2.3.2 Optional function
The relay has optional communication MODBUS RTU and IEC 60870-5-103
protocol on RS485 two wire.
2.4 Other Functions
2.4.1 Self-Supervision
The IED is provided with an extensive self-supervision system which continuously
supervises the software and the electronics. It handles run-time fault situations and
informs the user about a fault via the LHMI.

Table of Contents

Other manuals for ABB REF601

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF601 and is the answer not in the manual?

ABB REF601 Specifications

General IconGeneral
BrandABB
ModelREF601
CategoryProtection Device
LanguageEnglish

Related product manuals