Configurable Binary Outputs
individually configured as either Inverted or Non
configure for following different operating modes:
All above mode also supports Inverted (I) operation.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
Configurable Binary Outputs
individually configured as either Inverted or Non
configure for following different operating modes:
All above mode also supports Inverted (I) operation.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
Configurable Binary Outputs
individually configured as either Inverted or Non
configure for following different operating modes:
P
S
of the triggering signal.
H
si
Output can be reset by all possible reset input triggers
L
Output can be reset only by
All above mode also supports Inverted (I) operation.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
.
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
-
of the triggering signal.
Output can be reset by all possible reset input triggers
Output can be reset only by
All above mode also supports Inverted (I) operation.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
of the triggering signal.
Output can be reset by all possible reset input triggers
Output can be reset only by
All above mode also supports Inverted (I) operation.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
of the triggering signal.
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
Output can be reset only by
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
i
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
of the triggering signal.
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
Output can be reset only by
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
:
In pulse mode, the binary output activates for a fixed duration
of the triggering signal.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
Output can be reset only by
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
of the triggering signal.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
Output can be reset only by
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
of the triggering signal.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
5-
: Once output is activated, it will remain active even if
Output can be reset only by
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
-
availability of power, binary output configured as
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
of the triggering signal.
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
Output can be reset only by
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
-
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
.
: Once output is activated, it will remain active even if
Output can be reset only by
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
gnaling purpose), remaining can be
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
output BO4 is fixed to ā
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
output BO4 is fixed to ā
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
output BO4 is fixed to ā
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
individually configured as either Inverted or Non
-
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
output BO4 is fixed to ā
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
output BO4 is fixed to ā
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
output BO4 is fixed to ā
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
output BO4 is fixed to ā
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
output BO4 is fixed to ā
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
output BO4 is fixed to ā
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
o
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
>
>
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
ā
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
Breaker command operation) as well command available from MODBUS
Protection and Control Function
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
Protection and Control Function
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior