1MDU07212
REF601 / REJ601
Application Manual
4.11
1MDU07212
REF601 / REJ601
Application Manual
4.11
1MDU07212
REF601 / REJ601
Application Manual
4.11
1MDU07212
-
YN
REF601 / REJ601
Application Manual
YN
Rev. C
REF601 / REJ601
Application Manual
Rev. C
REF601 / REJ601
Application Manual
Rev. C
Configurable Binary Outputs
The relay
con
individually configured as either Inverted or Non
configure for following different operating modes:
1.
2.
3.
4.
All above mode also supports Inverted (I) operation.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
The signals availab
Ā·
Ā·
Ā·
Configurable Binary Outputs
The relay
con
tacts
individually configured as either Inverted or Non
configure for following different operating modes:
1.
2.
3.
4.
All above mode also supports Inverted (I) operation.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
The signals availab
Ā·
Ā·
Ā·
Configurable Binary Outputs
The relay
tacts
individually configured as either Inverted or Non
configure for following different operating modes:
P
ulse mode (P)
of 200 ms when
S
elf
of the triggering signal.
H
old mode (H)
si
gnal drops.
Output can be reset by all possible reset input triggers
L
ockout mode (L)
trigger signal drop.
Output can be reset only by
All above mode also supports Inverted (I) operation.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
The signals availab
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
IEC_103
Configurable Binary Outputs
The relay
tacts
.
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
ulse mode (P)
of 200 ms when
elf
-
reset mode (S)
of the triggering signal.
old mode (H)
gnal drops.
Output can be reset by all possible reset input triggers
a
b
c
ockout mode (L)
trigger signal drop.
Output can be reset only by
a
b
All above mode also supports Inverted (I) operation.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
The signals availab
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
IEC_103
Configurable Binary Outputs
The relay
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
ulse mode (P)
of 200 ms when
reset mode (S)
of the triggering signal.
old mode (H)
gnal drops.
Output can be reset by all possible reset input triggers
a
b
c
ockout mode (L)
trigger signal drop.
Output can be reset only by
a
b
All above mode also supports Inverted (I) operation.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
The signals availab
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
IEC_103
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
ulse mode (P)
of 200 ms when
reset mode (S)
of the triggering signal.
old mode (H)
gnal drops.
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset binary input
Reset command from optional communication module via MODBUS
/ IEC60870
ockout mode (L)
trigger signal drop.
Output can be reset only by
local HMI by reset key combination and
Reset binary input.
All above mode also supports Inverted (I) operation.
Operating mode for binary
i
nverted
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
During non
Inverted will ope
availability of power.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
The signals availab
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
IEC_103
or Front HMI
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
ulse mode (P)
of 200 ms when
reset mode (S)
of the triggering signal.
old mode (H)
gnal drops.
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset binary input
Reset command from optional communication module via MODBUS
/ IEC60870
ockout mode (L)
trigger signal drop.
Output can be reset only by
local HMI by reset key combination and
Reset binary input.
All above mode also supports Inverted (I) operation.
Operating mode for binary
nverted
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
During non
Inverted will ope
availability of power.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
The signals availab
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
or Front HMI
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
ulse mode (P)
:
In pulse mode, the binary output activates for a fixed duration
of 200 ms when
triggered
reset mode (S)
of the triggering signal.
old mode (H)
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset binary input
Reset command from optional communication module via MODBUS
/ IEC60870
ockout mode (L)
trigger signal drop.
Output can be reset only by
local HMI by reset key combination and
Reset binary input.
All above mode also supports Inverted (I) operation.
Operating mode for binary
nverted
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
During non
Inverted will ope
availability of power.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
The signals availab
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
or Front HMI
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
triggered
reset mode (S)
:
of the triggering signal.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset binary input
Reset command from optional communication module via MODBUS
/ IEC60870
-
ockout mode (L)
: Once output is activated, it will remain active even if
trigger signal drop.
Output can be reset only by
local HMI by reset key combination and
Reset binary input.
All above mode also supports Inverted (I) operation.
Operating mode for binary
nverted
Self
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
During non
Inverted will ope
availability of power.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
or Front HMI
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
triggered
:
In self
of the triggering signal.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset binary input
Reset command from optional communication module via MODBUS
-
5-
103
: Once output is activated, it will remain active even if
Output can be reset only by
local HMI by reset key combination and
Reset binary input.
All above mode also supports Inverted (I) operation.
Operating mode for binary
Self
-
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
During non
-
availability of power, binary output configured as
Inverted will ope
availability of power.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
or Front HMI
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
triggered
In self
of the triggering signal.
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset binary input
Reset command from optional communication module via MODBUS
103
: Once output is activated, it will remain active even if
Output can be reset only by
local HMI by reset key combination and
Reset binary input.
All above mode also supports Inverted (I) operation.
Operating mode for binary
-
Reset Mode.ā€
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
Inverted will ope
availability of power.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
In self
-
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset binary input
Reset command from optional communication module via MODBUS
103
.
: Once output is activated, it will remain active even if
Output can be reset only by
local HMI by reset key combination and
Reset binary input.
All above mode also supports Inverted (I) operation.
Operating mode for binary
Reset Mode.ā€
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
Inverted will ope
n and its status will be restored only after
availability of power.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
Reset Mode.ā€
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
availability of power.
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
Reset Mode.ā€
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
Except BO4 (reserved to IRF si
gnaling purpose), remaining can be
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
Operating mode for binary
output BO4 is fixed to ā€œ
Reset Mode.ā€
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
output BO4 is fixed to ā€œ
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
Configurable Binary Outputs
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
individually configured as either Inverted or Non
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
output BO4 is fixed to ā€œ
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
individually configured as either Inverted or Non
-
Inverted and also can be
configure for following different operating modes:
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
local HMI by reset key combination
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
output BO4 is fixed to ā€œ
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
Inverted and also can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
local HMI by reset key combination and
All above mode also supports Inverted (I) operation.
output BO4 is fixed to ā€œ
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
Inverted and also can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
output BO4 is fixed to ā€œ
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
Inverted and also can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Output can be reset by all possible reset input triggers
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
output BO4 is fixed to ā€œ
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
Inverted and also can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
output BO4 is fixed to ā€œ
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
Individual trip of protection functions I>, I>>, I>>>, Io> and I
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
Inverted and also can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
output BO4 is fixed to ā€œ
Non
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
le for triggering binary outputs are as follows:
Individual start of protection functions I>, I>>, I>>>, Io> and I
o
Individual trip of protection functions I>, I>>, I>>>, Io> and I
o
>
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Section 4
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
Inverted and also can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
Non
By default all binary outputs are NO (Normally Open).
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
o
>
>
>
>
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Section 4
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
Inverted and also can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
Non
–
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
n and its status will be restored only after
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
>
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Section 4
Protection and Control Function
has total six output contacts, two power contact and four signaling
gnaling purpose), remaining can be
Inverted and also can be
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
External trip (open) command available at binary input (configured for
Breaker command operation) as well command available from MODBUS
Section 4
Protection and Control Function
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
: Once output is activated, it will remain active even if
(Exception: BO1 in CEI configuration is NC (Normally Close)
availability of power, binary output configured as
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
Breaker command operation) as well command available from MODBUS
/
Section 4
Protection and Control Function
33
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior
The output remains in active state till trigger persists.
: Once output is activated, it will remain active even if trigger
Reset command from optional communication module via MODBUS
All binary outputs except BO4 can be triggered by different protection and control
signals. It is possible to map same signal to trigger more than one binary output.
/
Section 4
Protection and Control Function
33
In pulse mode, the binary output activates for a fixed duration
reset mode, the binary output follows the behavior

Table of Contents

Other manuals for ABB REF601

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF601 and is the answer not in the manual?

ABB REF601 Specifications

General IconGeneral
BrandABB
ModelREF601
CategoryProtection Device
LanguageEnglish

Related product manuals