2-6 Planning to Use Your ControlNet PLC-5 Processor
Table 2.B ControlNet Unscheduled Data-Transfer Operations
Operation Description Features
Non-discrete I/O
Data Transfer
CIO Instructions
Perform ladder-initiated unscheduled non-discrete I/O data transfers on
a ControlNet network by using ControlNet I/O Transfer (CIO) instructions.
The data type for these transfers (CT) has the following information:
Command:
1771 READ reads data from a 1771 non-discrete
I/O module
1771 WRITE writes data to a 1771 non-discrete
I/O module
1794 READ reads data from a 1794 I/O module
1794 WRITE writes data to a 1794 I/O module
1794 FAULT
ACTION changes the action a module takes
when it faults
1794 IDLE
ACTION changes the action a module takes
when it is idle
1794 CONFIG DATA changes a module’s configuration
data
1794 SAFE STATE DATA changes a modules safe-state data
CIP GENERIC sends user-specified CIP service
Generic bi-directional sends user-specified CIP service
which requires reply data
1747 READ INPUT reads data from SLC I/O module
input file
1747 WRITE OUTPUT writes data to SLC I/O module
output file
1747 READ M0 FILE reads data from SLC I/O module
M0 file
1747 WRITE M0 FILE writes data to SLC I/O module M0
file
1747 READ M1 FILE reads data from SLC I/O module
M1 file
1747 WRITE M1 FILE writes data to SLC I/O module M1
file
1747 SAFE STATE change SLC I/O module safe state
DATA data
1747 WRITE FLAGS change action SLC I/O module
take when it faults and/or goes to
idle
1747 CONFIG DATA change SLC module’s
configuration data
Data-table address in source processor
Size of message in words
Network address of destination node
Slot of destination module
Port number—set to 2 for the ControlNet network
Flags:
.TO forces a transfer to time out
.EW indicates that the transfer is waiting for an open connection
.CO transfer is made continuously in Run mode
.ER indicates that the transfer was terminated due to an error
.DN indicates that the transfer was made without error
.ST indicates that the transfer was started
.EN indicates that the transfer instruction is enabled
Error code—indicates the error when the.ER bit is set
2
Done length—indicates the number of words transferred
As many as 32 1771 READ and/or 1771 WRITE
CIOs can be active at a time
1
Minor fault bit S:17/14 is set when 32 1771
READ and/or 1771 WRITE CIOs are active at a
time
As many as a total of 8 1794 Flex I/O and 1747
SLC I/O CIOs can be active at a time
1
Minor fault bit S:17/15 is set when 8 1794 Flex
I/O CIOs are active at a time
Any transfer initiated from a Processor Input
Interrupt (PII) or Selectable Timed Interrupt (STI)
program suspends execution of the program
scan until the transfer is completed
Important: This can extend your program scan
by tens of milliseconds.
No transfer is initiated when the processor is in
Program mode
Transfers that have been running with the.CO
bit set automatically restart on the
Program-to-Run transition when the Continue
Last step bit is set and the data table has not
changed
A transfer has a maximum size of 64 words
If the SFC startover bit is set in the processor
configuration file, continuous CIOs may time out
if you cycle power in RUN mode. If this happens,
the CIO error bit is set. To reset the error bit, the
CIO instruction rung condition must go from
FALSE to TRUE.
See Chapter 4 and Appendices C and F for more
information.

Table of Contents

Other manuals for Allen-Bradley ControlNet PLC-5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ControlNet PLC-5 and is the answer not in the manual?

Allen-Bradley ControlNet PLC-5 Specifications

General IconGeneral
BrandAllen-Bradley
ModelControlNet PLC-5
CategoryController
LanguageEnglish

Related product manuals