1785-UM022B-EN-P - February 2002
Planning to Use Your ControlNet PLC-5 Processor 2-7
Using I/O Forcing Operations
ControlNet I/O forcing occurs in the same way as remote I/O forcing
in the ControlNet processors. The processor performs the forcing and
transmits the forced data to the output- and input-image tables. You
can force any discrete I/O data placed in the I/O image; however,
forcing of DIF and DOF data is not supported.
For detailed information about forcing, see your programming
software documentation.
Peer-to-peer
Messaging
MSG Instructions
You can use ControlNet message (MSG) instructions and the data-type
MG to create unscheduled messages that are initiated by one ControlNet
PLC-5 processor and sent to another ControlNet PLC-5 processor. The
MG data type for the ControlNet instruction has the following
information:
Command—PLC-5 TYPED READ, PLC-5 TYPED WRITE, PLC-3 WORD
RANGE READ, PLC-3 WORD RANGE WRITE, PLC-2 UNPROTECTED
READ, PLC-2 UNPROTECTED WRITE
Data-table address in source processor
Size of message in elements
Network address of destination processor
Data-table address in destination processor
Port number—set to 2 for the ControlNet network
Flags:
.TO forces a message to time out
.EW indicates that the message is waiting for an open connection
.CO message is sent continuously in Run mode
.ER indicates that the message was terminated due to an error
.DN indicates that the message was sent without error
.ST indicates that the message was started
.EN indicates that the message instruction is enabled
.NC forces the connection to close when the message is done
Error code—indicates the error when the.ER bit is set
2
As many as 32 ControlNet MSGs can be active
at a time
1
Minor fault bit S:17/13 is set when 32
ControlNet MSGs are active at a time
All messages have the same priority
No message is initiated when the processor is
in Program mode
Messages that have been running with the.CO
bit set automatically restart on the Program-
to-Run transition when the Continue Last step
bit is set and the data table has not changed
Each message has a maximum size of 1000
elements
See chapter 4 and Appendices C and F for more
information.
1
Because connections are opened and closed as needed, more can exist in a program as long as no more than this number are active at one time.
2
See Appendix D for a list of ControlNet error codes.
Operation Description Features
AB Drives

Table of Contents

Other manuals for Allen-Bradley ControlNet PLC-5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ControlNet PLC-5 and is the answer not in the manual?

Allen-Bradley ControlNet PLC-5 Specifications

General IconGeneral
BrandAllen-Bradley
ModelControlNet PLC-5
CategoryController
LanguageEnglish

Related product manuals