Publication 1762-UM001D-EN-P - March 2004
6-4 Using Real-Time Clock and Memory Modules
Program Compare
The memory module can also provide application security, allowing
you to specify that if the program stored in the memory module does
not match the program in the controller, the controller will not enter
an executing (run or test) mode. To enable this feature, set the S:2/9
bit in the system status file. See “Status System File” in the MicroLogix
1200 and 1500 Programmable Controllers Instruction Set Reference
Manual, Publication 1762-RM001 for more information.
Data File Download Protection
The memory module supports data file download protection. This
allows user data to be saved (not overwritten) during a download.
Memory Module Write Protection
The memory module supports write-once, read-many behavior. Write
protection is enabled using your programming software.
Removal/Insertion Under Power
The memory module can be installed or removed at any time without
risk of damage to either the memory module or the controller. If a
memory module is installed while the MicroLogix 1200 is executing,
the memory module is not recognized until either a power cycle
occurs, or until the controller is placed in a non-executing mode
(program mode, suspend mode or fault condition).
TIP
Data file download protection is only functional if the
processor does not have a fault, size of all protected
data files in the memory module exactly match the
size of protected data files within the controller, and
all protected data files are of the same type. See
“Protecting Data Files During Download” in the
MicroLogix 1200 and 1500 Programmable Controllers
Instruction Set Reference Manual, Publication
1762-RM001.
IMPORTANT
Once set, write protection cannot be removed. A
change cannot be made to the control program
stored in a write protected memory module. If a
change is required, use a different memory module.

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1200 and is the answer not in the manual?

Allen-Bradley MicroLogix 1200 Specifications

General IconGeneral
BrandAllen-Bradley
ModelMicroLogix 1200
CategoryControl Unit
LanguageEnglish

Related product manuals