EasyManuals Logo
Home>Allen-Bradley>Controller>PowerFlex 70

Allen-Bradley PowerFlex 70 Quick Start Quide

Allen-Bradley PowerFlex 70
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
English-10 PowerFlex 70 Adjustable Frequency AC Drive Quick Start
Step 5 Program the Drive – Parameter Files & Groups
Inputs & Outputs
File J
Communication
File H
Utility
File E
Dynamic Control
File D
Speed Command
File C
Motor Control
File B
Monitor
File A
Metering
Drive Data
Motor Data
Torq Attributes
Volts per Hertz
Speed Feedback*
Spd Mode & Limits
Speed References
Discrete Speeds
Speed Trim
Slip Comp
Process PI
Speed Regulator*
Ramp Rates
Load Limits
Stop/Brake Modes
Restart Modes
Power Loss
Direction Config
HIM Ref Config
MOP Config
Drive Memory
Diagnostics
Faults
Alarms
Comm Control
Masks & Owners
Datalinks
Security*
Analog Inputs
Analog Outputs
Digital Inputs
Digital Outputs
*Enhanced Control Only.
Frequently Used Parameters
MOTOR CONTROL (File B)
Motor Data
041 [Motor NP Volts]
Set to the motor nameplate rated volts.
Default:
Min/Max:
Units:
Drive Rating Based
0.0/[Rated Volts]
0.1 VAC
042 [Motor NP FLA]
Set to the motor nameplate rated full load
amps.
Default:
Min/Max:
Units:
Drive Rating Based
0.0/[Rated Amps] × 2
0.1 Amps
047
048
045 [Motor NP Power]
Set to the motor nameplate rated power.
Default:
Min/Max:
Units:
Drive Rating Based
0.00/100.00
0.00/412.48
0.01 kW/HP
See [Mtr NP Pwr Units]
046
046 [Mtr NP Pwr Units]
Selects the motor power units to be used.
Default:
Options: 0
1
Drive Rating Based
“Horsepower”
“kiloWatts”
047 [Motor OL Hertz]
Selects the output frequency below
which the motor operating current is
derated. The motor thermal overload will
generate a fault at lower levels of current.
Default:
Min/Max:
Units:
Motor NP Hz/3
0.0/500.0 Hz
0.1 Hz
042
220
Torq Attributes
053 [Torque Perf Mode]
Sets the method of motor torque
production.
Default:
Options:
0
0
1
2
3
“Sensrls Vect”
“Sensrls Vect”
“SV Economize”
“Custom V/Hz”
“Fan/Pmp V/Hz”
062
063
069
070
[Motor Cntl Sel]
Sets the method of motor control used in
the drive.
Important: “FVC Vector” mode requires
autotuning of the motor, both coupled
and uncoupled to the load.
(1)
Enhanced firmware 2.001 & later.
Default:
Options:
0
0
1
2
3
4
“Sensrls Vect”
“Sensrls Vect”
“SV Economize”
“Custom V/Hz”
“Fan/Pmp V/Hz”
“FVC Vector”
(1)
32
E C
Standard
E C

Other manuals for Allen-Bradley PowerFlex 70