LEGIONNAIRE’S DISEASE PROTECTION
enabled/disabled via installer menu (P5
LEGIONNAIRE’S DISEASE PROTECTION
dangerous bacteria in the sanitary water tank heating the water until bacteria deadly
conditions occur.
It will be activated if P5 parameter
is ON and one of these two conditions occur alternatively:
57 °C for 15 consecutive minutes never occurred for 3 days after
≥ 57 °C for 15 consecutive minutes never occurred for 30 days
LEGIONNAIRE’S DISEASE PROTECTION
simultaneously satisfied:
• T
water
= 65 °C (or T
set-point
57 °C for at least 15 minutes
As these temperatures may cause burns, it is advisable to use a thermostatic mixer.
is different from 65 °C, the target temperature is temporarily set to 65 °C and it will come back to the previous value
when the antibacterial procedure stops.
If the ON/OFF button is pushed during this procedure, it
If an error occurs during this procedure, it
will be stopped and postponed of 3 days.
When the device is working in
•
AUTO or BOOST mode: both conditions are reached by standard procedures
e: the electrical resistance
VOYAGE mode: the procedure shall never be perfo
Device OFF state: the procedure shall never be performed until the device is turned ON
DEFROST function
This function can be enabled
/disabled via installer menu
ensures good performances also in winter or with cold climate
conditions, reversing temporarily the heating cycle (see picture).
if these two conditions occur:
• The Heat Pump is working (T
water
• The Evaporator is clogged
by ice (Temperature on evaporator
and the air temperature is below 15°C)
During the function, the heating element could turn on (i.e. if the Antifreeze function will
occur, see next paragraph).
ANTIFREEZE function
This function is activated by default.
The antifreeze procedure shall performed in order to avoid water freezing into the tank
The device receives power from mains (
ves the electrical resistance (1
LEGIONNAIRE’S DISEASE PROTECTION
enabled/disabled via installer menu (P5
LEGIONNAIRE’S DISEASE PROTECTION
process avoids the proliferation of
dangerous bacteria in the sanitary water tank heating the water until bacteria deadly
The waves symbol means that the
achieved temperature is above T
is ON and one of these two conditions occur alternatively:
57 °C for 15 consecutive minutes never occurred for 3 days after
≥ 57 °C for 15 consecutive minutes never occurred for 30 days
LEGIONNAIRE’S DISEASE PROTECTION
process leap water temperature until the two following conditions are
57 °C for at least 15 minutes
As these temperatures may cause burns, it is advisable to use a thermostatic mixer.
is different from 65 °C, the target temperature is temporarily set to 65 °C and it will come back to the previous value
If the ON/OFF button is pushed during this procedure, it
will be stopped and postponed of 30 da
will be stopped and postponed of 3 days.
AUTO or BOOST mode: both conditions are reached by standard procedures
e: the electrical resistance
(1200 W) probably will be switched on
VOYAGE mode: the procedure shall never be perfo
rmed until VOYAGE days are over
Device OFF state: the procedure shall never be performed until the device is turned ON
/disabled via installer menu
(P7 Parameter: default = ON).
ensures good performances also in winter or with cold climate
conditions, reversing temporarily the heating cycle (see picture).
if these two conditions occur:
by ice (Temperature on evaporator
and the air temperature is below 15°C)
During the function, the heating element could turn on (i.e. if the Antifreeze function will
The antifreeze procedure shall performed in order to avoid water freezing into the tank
The device receives power from mains (
GREEN functioning and device OFF state).
ves the electrical resistance (1
The waves symbol means that the
achieved temperature is above T
process leap water temperature until the two following conditions are
is different from 65 °C, the target temperature is temporarily set to 65 °C and it will come back to the previous value
GREEN functioning and device OFF state).